Input signal (calibrated switchable) |
0 to 20 mA, 4 to 20 mA, 0 to 5 V, 0 to 10 V, 1 to 5 V, 2 to 10 V | |
Input resistance | Current input Voltage input |
≤ 35 Ohm ≥ 100 kOhm |
Overload | Current input Voltage input |
< 50 mA < 30 V |
Transmitter supply Tx (switchable) |
16 V (open circuit voltage/short circuit current ≤ 22 V/35 mA) |
Output signal (calibrated switchable) |
0 to 20 mA, 4 to 20 mA, 0 to 5 V, 0 to 10 V, 1 to 5 V, 2 to 10 V | |
Load | Current output: ≤ 6 V (300 Ohm at 20 mA) | Voltage output: ≤ 5 mA (2 kOhm at 10 V) |
Linear transmission range | -1 to +110 % | |
Residual ripple | < 10 mVrms |
Transmission error | < 0.1 % full scale | |
Temperature coefficient 1) | < 100 ppm/K | |
Cut-off frequency -3 dB | 5 kHz | |
Response time T99 | 150 µs | |
Test voltage | 3 kV AC, 50 Hz, 1 min, Input against Output I against Output II against power supply | |
Working voltage 2) (Basic Insulation) |
600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1 | |
Protection against electrical shock | Protective separation according to EN 61140 by reinforced insulation in accordance with EN 61010-1 up to 300 V AC/DC for overvoltage category II and pollution degree 2 between all circuits. | |
Ambient temperature | Operation Transport and storage |
–25 °C to +70 °C (-13 to +158 °F) –40 °C to +85 °C (-40 to +185 °F) |
Power supply | 24 V DC, voltage range 16.8 V to 31.2 V DC, approx. 1.4 W | |
EMC 3) | EN 61326-1 | |
Approvals | UL (USA/Canada): UL 61010, Class I, Div. 2 ATEX / IECEx: Zone 2 (nA) |
|
Construction | 6.2 mm (0.244") housing, protection class: IP 20 mounting on 35 mm DIN rail acc. to EN 60715 |
|
Weight | Approx. 70 g |